Fire Resistant Cables for Emergency Circuits

fire-resistant-cable2

Tai Sin’s FRA-XOL(E) Cables are designed to meet the requirements as described in BS 5839-1:2002+A2:2008, clause 26.2. This range also meets the PH120 class when tested in accordance with BS EN 50200:2006 and the 120 minutes survival time when tested in accordance with BS 8434-2:2003+A2:2009. In addition, the cable also complies with BS 6387 Cat. C.W.Z.

These cables are manufactured with plain annealed copper in either solid or stranded form. The conductors are protected with a fire barrier tape and are insulated with a Low Smoke Zero Halogen (LSZH) thermosetting compound. The cores are held together with a laminated aluminum tape screen which is bonded together with a LSZH sheath and at the same time comes into contact with a tinned copper conductor which acts as a circuit protective conductor and as a screen drain wire. These cables are manufactured to meet the requirements of BS 7629-1:2008.

Range : 2 cores to 4 cores: 1.0mm2 to 4.0mm2

Fire Performance Standards Achieved

Circuit Integrity :
- BS 5839-1:2002+A2:2008 Clause 26.2
- BS 8434-2:2003+A2:2009
- BS EN 50200:2006 PH120
- SS 299 Cat C.W.Z, BS 6387 Cat C.W.Z., IEC 60331

Flame Propagation : BS EN 60332-1-2 / BS EN 60332-3C / BS EN 50266

Acid Gas Emission : IEC 60754, BS EN 50267

Smoke Emission : IEC 61034, BS EN 61034